HE670ADC840 | General Electric | Analog isolation input module en Fujian, China

Especificaciones

Condición
nuevo
Dimensions
6.8x13.1cmx13.5cm
Weight
0.65 kg
Mfr. part number
HE670ADC840
Contact details
E-mail: Skype:dddemi33 Whatsapp/Wechat:+86 18030235313 Manager: Tiffany
Open circuit detection time
5 seconds max. Open circuit detection is available for all configurations except +/- 20mA current, 0-20mA current, and +/-10V voltage.
Max overvoltage
+/-14.5VDC continuous
Max overcurrent
28 mA continuous
Normal mode noise rejection
95 dB minimum @ 50/60 Hz with 8 Hz filter 85 dB minimum @ 50/60 Hz with 12 Hz filter
Common mode noise rejection
120dB minimum @ 50/60 Hz with 8 Hz filter 110dB minimum @ 50/60 Hz with 12 Hz filter
Settling time to 5% of full scale (notch filter dependent)
<80 mS
Calibrated accuracy at 25°c
Better than 0.1% of range (except 10 ohm CU RTD) Accuracy depends on A/D filter, data format, input noise, and ambient temperature.
Calibration interval
12 months typical to meet accuracy specifications over time. Module will allow for user offset to be applied as a periodic calibration adjustment.
Input offset drift with temperature
3.0 milliohm/°C maximum 2.0 uV/°C maximum
Gain drift with temperature
50 ppm/°C typical (90 ppm/°C maximum)
Module error over full temp range
0.5% of range typical (depends on range) 1.0% of range maximum
Module scan time (notch filter dependent)
(Assumes 2 ADC’s running in parallel, no CJC or lead resistance) 10 ms per Channel × 4 Channels = 40 ms (1K Hz filter) 127 ms per Channel × 4 Channels = 508 ms (8 Hz filter) Channels that are disabled are not scanned, shortening scan time.
Module conversion method
Sigma-delta
Isolation voltage channel to channel group to group terminal block to backplane/chassis
Opto-isolated, transformer isolated +-12.5Vdc channel to channel Tc/V/I/RTD 250 VAC continuous/1500 VAC for 60 seconds 250 VAC continuous/1500 VAC for 60 seconds
Subcategoría
Plc
ID de Anuncio
101736961

Descripción

Electric Field Control Analog Module
The HE670ADC840 provides eight analog channels with a resolution of 12-bits
Isolation levels are 400VDC (channel-to-channel) and 1,000VDC (channel-to-ground). The module changes the current input signals into digital values, which can be accessed through communications with the Bus Interface Unit.
These modules are protected within the standard Field Control I/O case and are compatible with a variety of I/O bases providing flexible termination options.
Technical Specifications

Power Consumption 130mA from backplane
Number of channels 8
Range 4-20mA
Channel-to-Channel Isolation 400VDC
Channel-to-Bus Isolation 1,000VDC
Input Impedance 100 ohms
Output Format Set by BIU
Resolution 12-bits
Maximum error at 25°C ± 1% Full Scale
Operating Temperature 0 to 75°C
Relative Humidity 5% to 95%, non-condensing
Input Power Required Supplied by BIU